Manual model IndAC
4 Solving
problems
4.1.1 General
If the air curtain does not work, or not
properly, perform the checks mentioned
below.
If that does not help, there may be a defect.
In that case, alert the installer.
4.1.2 Unit does not discharge any air
1 Check whether the air curtain has been
switched on by the control unit: see the
control unit documentation.
2 Check if the unit is not disabled by an
external control component (door switch
or room thermostat).
3 Check if mains power is supplied.
4 Reset the thermal protector of the fans
to: see the control unit documentation.
4.1.3 Unit discharges little air
1 Remove obstacles in front of intake and
discharge openings.
2 Check the heat exchanger for
contamination. Clean it if necessary.
3 Check the direction of rotation of the
fans.
Wrong: the blades go
forward
Correct: the blades go
backward
If necessary, correct the direction of
rotation by interchanging the connections
of two phases from the mains supply.
4.1.4 Unit does not heat, or too little
1 When facing draught: select a higher fan
speed using the operation switch.
2 Does the unit blow out enough air? If not,
perform the checks in sections 4.1.2 and
4.1.3.
For water-heated units:
3 Check the operation of the CH system.
For electrically heated units:
4 Check whether the isolating switch on all
units is set to position 1.
5 Check if mains power is supplied to each
unit.
6 Reset the high-limit thermostat: see the
control unit documentation
7 Check the control knob 1 in the unit: it
must always be set to 60° C.